Asymmetry Relay
AK 9840
The asymmetry relais AK 9840 of the VARIMETER series monitors voltage asymmetry, under voltage, phase failure as well as incorrect phase sequence at three-phase mains. The measurement is very simple and can be carried out without much wiring effort, as no separate auxiliary voltage is required. Early detection of impending failtures and preventive maintenance prevent costly damage and as a user you benefit from the operational safety and high availability of your system.
| 1- / 3-phase: | 3 |
|---|---|
| Enclosure design: | Switch cabinet |
| Measuring range max.: | 3 AC 690 V |
| Operate delay: | Yes |
| Output contacts: | 2 C/O contacts |
| Standard measuring range: | 3 AC 400 V |
| Width: | 70 mm |
| Type: | AK 9840 |
- According to IEC/EN 60255-1
- For nominal voltages from 3 AC 110 up to 690 V
- Detection of
- Voltage asymmetry
- Incorrect phase sequence
- Phase failure
- Undervoltage - Voltage feedback recognition
- Also suitable for harmonic industrial mains
- Closed circuit operation
- Contact position indication
- With adjustable delay
- 2 C/O contacts
- Width: 75 mm