Skip to main content Skip to search Skip to main navigation
Menu
Description

The sensorless standstill monitor UG 9146 is used for sensorless monitoring of electric motors for standstill. It measures the induced voltage of the coasting motor at 2 terminals of the stator winding. If the induced voltage approaches 0, this means motor standstill for the device and the output relay switches on.

Technical specifications
Auxiliary voltage: DC
Classification: Sensorless, Stillstandsüberwachung
Enclosure design: Switch cabinet
Measuring range max.: 4 V, 400 mV
Operate delay: Yes
Output contacts: 1 NC contact, 2 NO contacts
Width: 22,5 mm
Type: UG 9146
Advantages / Customer benefits
  • Fast reaction time
  • Easy to retrofit
  • No external sensors necessary
Features
  • According to EN 60 255-1
  • Standstill detection on 3- and single-phase motors
  • Independent of direction
  • Broken wire detection
  • Forcibly guided safety contacts:
    - 2 NO contacts for AC 250 V
    - 1 NC contact for DC 24 V
  • Adjustable voltage setting
  • Adjustable standstill time delay
  • LED indicators for standstill, event of line breakage and operation voltage
  • Suitable for operation with inverters
  • Removable terminal strips:
    - UG 9146 PS: plug in screw terminals
    - UG 9146 PC: plug in cage clamp terminals
  • Width: 22.5 mm