Skip to main content Skip to search Skip to main navigation
Menu
Description

The voltage and frequency module RP 9810 monitors in domestic generator sets the mains of the energy supplier. It is built up in a redundant way and each of the 2 channels act on a separate output relay. The adjustment is made via rotational switches. The factory default setting is according to the description in VDE-AR-N 4105:2011-08.

Technical specifications
1- / 3-phase: 3
Auxiliary voltage: Without
Enclosure design: Distribution board
Operate delay: Yes
Output contacts: 3 C/O contacts
Supply voltage: 3/N AC 400/230 V
Type: RP 9810
Width: 70 mm
Advantages / Customer benefits
  • Easy adjustment via rotational switch
  • Precise adjustment and indication of setting values
  • Indication, diagnostics and fault presentation via display
  • Protection against manipulation by sealable transparent cover over setting switches
  • Mains and system protection for your generator set
Features
  • According to VDE-AR-N 4105:2011-08
  • Following DIN VDE 0126-1-1:2013-08
  • According to DIN EN 60255-1
  • Can be used according to EEG 2012 and SysStabV
  • Voltage and frequency monitoring for generator sets >30 kVA on public grid, as option also for ≤ 30kVA
  • Fail-safe because of 2-channel structure
  • Certificate of conformity (test certificate) of the BG ETEM
  • Monitoring of the section switches with measuring of response time
  • System test via test button
  • Isolated grid detection
  • Manual reset
  • With additional enabling input, e.g. for ripple control receiver
  • Connection or re-connection after adjustable delay time tw
  • Factory setting according to VDE-AR-N 4105:2011-08
  • Random controlled disconnection in the range of 50.2 Hz and 51.5 Hz for non-regulated power generation systems
  • Protection against manipulation by sealable transparent cover over setting switches
  • Additional fault signalling relay output
  • High measuring accuracy
  • Installion type enclosure 4TE (width x height x depth: 70 x 90 x 71 mm)