Voltage and frequency monitor according to VDE-AR-N 4105:2011-08
RP 9810
The voltage and frequency module RP 9810 monitors in domestic generator sets the mains of the energy supplier. It is built up in a redundant way and each of the 2 channels act on a separate output relay. The adjustment is made via rotational switches. The factory default setting is according to the description in VDE-AR-N 4105:2011-08.
| 1- / 3-phase: | 3 |
|---|---|
| Auxiliary voltage: | Without |
| Enclosure design: | Distribution board |
| Operate delay: | Yes |
| Output contacts: | 3 C/O contacts |
| Supply voltage: | 3/N AC 400/230 V |
| Type: | RP 9810 |
| Width: | 70 mm |
- Easy adjustment via rotational switch
- Precise adjustment and indication of setting values
- Indication, diagnostics and fault presentation via display
- Protection against manipulation by sealable transparent cover over setting switches
- Mains and system protection for your generator set
- According to VDE-AR-N 4105:2011-08
- Following DIN VDE 0126-1-1:2013-08
- According to DIN EN 60255-1
- Can be used according to EEG 2012 and SysStabV
- Voltage and frequency monitoring for generator sets >30 kVA on public grid, as option also for ≤ 30kVA
- Fail-safe because of 2-channel structure
- Certificate of conformity (test certificate) of the BG ETEM
- Monitoring of the section switches with measuring of response time
- System test via test button
- Isolated grid detection
- Manual reset
- With additional enabling input, e.g. for ripple control receiver
- Connection or re-connection after adjustable delay time tw
- Factory setting according to VDE-AR-N 4105:2011-08
- Random controlled disconnection in the range of 50.2 Hz and 51.5 Hz for non-regulated power generation systems
- Protection against manipulation by sealable transparent cover over setting switches
- Additional fault signalling relay output
- High measuring accuracy
- Installion type enclosure 4TE (width x height x depth: 70 x 90 x 71 mm)