Passer au contenu principal Passer à la recherche Passer à la navigation principale
Menu
Description

The Load monitor MK9397 and MH9397 of the varimeter family monitor reliably the load of motors as well as the function of 3 phase electrical users. If the measured value falls under or goes over the adjusted settings the corresponding output relay is energised. To avoid unnecessary tripping a response delay tv can be adjusted between 0 and 10 s. LEDs show the status of the output relays.

Caractéristiques techniques
Boîtier montage: Switch cabinet
Contacts de sortie: 2 x 1 C/O contacts
Largeur utile: 45 mm
Mono- / triphasé: 3
Plage de mesure max: 12 A (8 kW)
Retard à l´appel réglable: Oui
Tension aux: AC
Type: MH 9397
Avantages / Bénéfices clients
  • Preventive maintenance
  • For a evaluate time
  • Quicker fault locating
  • Precise and reliable
  • Overload detection, as option also with prewarning
  • Can also be used for underload monitoring
  • Simple adjustment and fault diagnostics
  • Space and cost saving
Caractéristiques
  • According to EN 60255-1
  • Active power measuring
  • Relay output
    MK 9397N: 1 changeover contact
    MH 9397: 1 changeover contact each for overload and prewarning
  • On delay
  • Closed circuit operation
  • As option open circuit operation
  • As option with plugable terminal blocks for easy exchange of devices
    - with screw terminals
    - or with cage clamp terminals
  • MK 9397N: Width 22,5 mm
    MH 9397: Width 45 mm