Dold Italia S.r.l.

Via Privata Passo Pordoi, 5
20139 Milano
Italia
RP 5995

New- / First- / Common Signal Annunciator

RP 5995

Contacts

Nominal voltage

Terminal type

Variant

  • 0060032
  • RP5995S DC24V ERWEITERUNGSMODUL
Extension module RP 5995 altro

Descrizione del prodotto

Extension module RP 5995

Specifiche tecniche

Width: 70 mm
Alarm inputs: 8
Alarm inputs extendable up to: 88
Operating principle: Energized on trip, De-energized on trip
Operate delay: Yes
Special features: Bus-compatible, Configurable
Enclosure design: Distribution board
Optional buzzer: Yes
Optical signal: LED
Type: RP 5995

Merkmale

  • New- / First- /Common Signal Annunciator RP 5994, RP 5995
  • Fast localisation of failures and their causes
  • Reduction of standstill times in production
  • Adjustable operating modes:
    - New- / First signal annunciator according to DIN 19 235,
    - Common alarm annunciator manual reset / auto reset settable
  • Expandable from 8 to 88 fault signals
  • Open or closed circuit operation settable
  • Adjustable on delay for input signals 0 to 10 sec
  • Reset buttons for audible alarm and common alarm on front side
  • Connection for external reset of audible alarm, common alarm and single alarm according to setting
  • Galvanic separation to bus RS485 (optional)
  • Accessories: buzzer RK 8832, display unit EH 5994, EH 5995, text display unit EH 5996
  • Width: 70 mm
  • Base module RP 5994:
    - 8 fault signal inputs with indicator LED on the unit
    - One relay output each for audible alarm and common alarm
    - Reset buttons for audible alarm, common alarm, and single alarm
    - Connection of remote reset button. Function according to setting
  • Extension module RP 5995:
    - 8 fault signal inputs with indicator LED on the unit
    - One relay output each for audible alarm and common alarm (on request)
    - Reset buttons for audible alarm, common alarm, and single alarm
    - Connection of remote reset button. Function according to setting