Dold Italia S.r.l.

Via Privata Passo Pordoi, 5
20139 Milano
Italia
RN 5893/100

Insulation monitor

RN 5893/100

Contacts

Auxiliary voltage

Alarm value

Prewarning value

Approvals and Markings

Variant

  • 0069880
  • RN5893.12/100/61 ACDC24-60V 1K-500K
The insulation monitor RN 5897/100 of the VARIMETER IMD family is a solution for optimal... altro

Descrizione del prodotto

The insulation monitor RN 5897/100 of the VARIMETER IMD family is a solution for optimal insulation monitoring of modern IT systems. The device can be used in the most flexible way for AC, DC and AC/DC systems. Mains areas of applications are non-earthed DC charging stations for electric vehicles with mains voltages up to DC 1000 V, that need an extended temperature range. The setting of the parameters and the switching values is done via Modbus. All measured values, device statuses and parameters can also be read out via Modbus. All functions of the device can also be operated via Modbus. The operating status is indicated user friendly via a multicolour LED. With a sealable transparent cover the device is protectet against manipulation.

Specifiche tecniche

Width: 52,5 mm
Classification: For DC charging stations
Response value: 1 - 500 kΩ
IMD type: AC, DC, AC/DC
Nominal voltage IT system: AC 0 - 230, AC 0 - 690 (Coupling device), DC 0 - 230, DC 0 - 1000 (Coupling device) V
Auxiliary voltage: AC/DC
Earth fault indicator: Yes
Approvals: UL-Recognized
Response value type: Adjustable
Enclosure design: Distribution board
Type: RN 5893/100

Vorteile / Kundennutzen

  • Suitable for DC charging stations for electric vehicles acc. to IEC/EN 61851-23:2014/AC:2016-06
  • Insulation monitoring according to IEC/EN 61557-8
  • Universal application in non-earthed AC-, DC-, AC/DC networks up to AC max. 250 V resp. DC max. 300 V
  • Connection of an external coupling device RP 5898 for voltages up to AC 690 V / DC 1000 V possible
  • Extended operating temperature range of - 40 ... + 70 °C
  • Very fast reaction time ≤ 1 s
  • Optimised insulation resistance monitoring also during mains voltage variation
  • Preventive fire and system protection
  • Detection of symmetric and asymmetric insulation faults
  • Easy adjustment of response values and setting parameter via Modbus
  • Suitable for leakage capacitances up to 5 μF
  • Monitoring also with voltage-free mains
  • Measuring circuit L(+)/L(-) with broken wire detection (can be switched off)
  • Protective conductor PE1/PE2 with broken wire detection (can't be switched off)
  • With galvanic separated Modbus RTU interface

Merkmale

  • 2 separate adjustable response thresholds (using e.g. for pre-alarm and Alarm)
  • Setting range pre-alarm: 1 kΩ … 500 kΩ
  • Setting range alarm: 1 kΩ … 500 kΩ
  • 2 parameterizable changeover contacts (for insulation fault pre-alarm, insulation fault-alarm, insulation fault-alarm on DC+/DC- or device fault) each galvanic separated
  • Energized or de-energized on trip can be selected for indicator relay
  • With multicolour status LED to indicate the state of operation.
  • Manual device self-test (automatic device self-test can be activated)
  • Alarm storage selectable
  • Protection against manipulation by sealable transparent cover
  • External control input for combined test- / reset-button with additional Stop of the measuring function
  • 2 wide voltage input for auxiliary voltage
  • Width 52.5 mm