Dold Italia S.r.l.

Via Privata Passo Pordoi, 5
20139 Milano
Italia
RN 5897

Insulation monitor

RN 5897

Contacts

Auxiliary voltage

Alarm value

Prewarning value

Approvals and Markings

Variant

  • 0070034
  • RN5897.12/61 DC12-24V 15K-100K
The insulation monitor RN 5897 of the VARIMETER IMD family is a solution for optimal insulation... altro

Descrizione del prodotto

The insulation monitor RN 5897 of the VARIMETER IMD family is a solution for optimal insulation monitoring of modern IT systems. The device can be used in the most flexible way for AC, DC and AC/DC systems even with large leakage capacity to earth (PE). The adjustment of the setting values is simple and user friendly done on 2 rotary switches on the front of the device. Via display and LEDs the measured value, device parameters and device status are indicated easy to read. With a sealable transparent cover the device is protectet against manipulation.

Specifiche tecniche

Width: 52,5 mm
Response value: 1 - 100 kΩ
IMD type: AC, DC, AC/DC
Nominal voltage IT system: AC 0 - 230, DC 0 - 230 V
Auxiliary voltage: DC, AC/DC
Earth fault indicator: Yes
Approvals: UL
Response value type: Adjustable
Enclosure design: Distribution board
Type: RN 5897

Vorteile / Kundennutzen

  • Acc. to DIN VDE 0100-551 for mobile generator sets
  • Preventive fire and system protection
  • Detection of symmetric and asymmetric insulation faults
  • Quick fault localisation through selective earth fault detection to L+ and L-
  • Universal application in non-earthed AC, DC, AC/DC networks up to 300 V
  • Easy adjustment of response values and setting parameter via rotational switch and menu display
  • Suitable for large leakage capacitances up to 300 μF
  • Optimised reaction time for large leakage capacitances
  • Monitoring also with voltage-free mains
  • Measuring circuit L(+)/L(-) with broken wire detection (can be switched off)
  • Protective conductor PE1/PE2 with broken wire detection (can't be switched off)
  • No additional coupling device required

Merkmale

  • Insulation monitoring according to IEC/EN 61557-8
  • 2 separate adjustable response thresholds (using e.g. for pre-Alarm and Alarm)
  • Setting range of 1st response value (Pre-Alarm): 20 kΩ … 500 kΩ
  • Setting range of 2nd response value (Alarm): 15 kΩ … 100 kΩ
  • 2 changeover contacts für insulation failures-Pre-Alarm and -Alarm
  • Energized or de-energized on trip can be selected for indicator relay
  • Display for indication of measured value, device parameters and device status
  • Setting the maximum leakage capacitance to shorten the response time
  • Automatic and manual device self-test
  • Alarm storage selectable
  • Protection against manipulation by sealable transparent cover
  • External control input for combined Test-/Reset-button
  • 3 wide voltage input for auxiliary voltage
  • Width 52.5 mm