Emergency stop module BN 5930.48/204 Advantages . Can be used for long leads in the e-stop loop. This allows a long distance between e-stop module and the e-stop button. . Crossfault detection in the e-stop circuit Features . According to - Performance Level (PL) e and category 4 to EN ISO 13849-1 - SIL Claimed Level (SIL CL) 3 to IEC/EN 62061 - Safety Integrity Level (SIL) 3 to IEC/EN 61508 . BN 5930.48/203 with cross fault detection by connecting 2 different phases, max. 400 V, BN 5930.48/204 with cross fault detection by connecting phase and neutral, max. 230 V . Dual voltage version . Emergency-stop circuit T12, T22: optionally for AC 110 V / DC 60 V or AC 230 V / DC 110 V . Output: 3 NO, 1 NC contacts for AC 400 V . 1-channel or 2-channel circuit . LED displays for channel 1, 2 and mains . Feedback circuit X1 - X2 for monitoring external contactors . Removable terminal strips . Width 100 mm Technical specifications Suited as safety gate monitor: Yes Cat. / PL acc. to EN ISO 13849-1: 4/e 1- / 2-channel: 1, 2 Connection: Pluggable screw terminals Output contacts max.: 1 NC contact, 3 NO contacts Width: 100mm Cross fault detection: Yes SIL CL acc. to IEC/EN 62061: 3 Nominal voltage: AC, DC Thermal current Ith max.: 10A Type: BN 5930.48/204 Manufacturer: E. Dold & Söhne GmbH & Co. KG Type: BN5930.48/204 AC110V 50/60HZ/ DC60V Art. No.: 0044713