Emergency stop module LG 5925 . Protection of people and machines . Emergency stop circuits on machines . Monitoring of safety gates . Usage in furnace application in continuous operation acc. to EN 50156-1 . Safe disconnection of the complete fuel supply in furnace applications according to EN 50156-1 section 10.5.5.2 Features . According to - Performance Level (PL) e and category 4 to EN ISO 13849-1 - SIL Claimed Level (SIL CL) 3 to IEC/EN 62061 - Safety Integrity Level (SIL) 3 to IEC/EN 61508 and IEC/EN 61511 . According to EN 50156-2 for furnaces . Output: max. 4 NO contacts, see contacts . LG 5925.54: 1 semiconductor output . Single and 2-channel operation . Line fault detection on On-button . Manual restart or automatic restart, switch S2 . With or without cross fault monitoring in the E-stop loop, switch S1 . LG 5925.54: with cross fault monitoring in the E-stop loop . LED indicator for channel 1, 2 and supply voltage . Removable terminal strips . Wire connection: also 2 x 1.5 mm2 stranded ferruled, or 2 x 2.5 mm2 solid DIN 46228-1/-2/-3/-4 . As option with pluggable terminal blocks for easy exchange of devices - With screw terminals - Or with cage clamp terminals . Width: 22.5 mm Technical specifications Suited as safety gate monitor: Yes Cat. / PL acc. to EN ISO 13849-1: 4/e 1- / 2-channel: 1, 2 Connection: Screw terminals, Pluggable screw terminals, Pluggable cage clamp terminals Output contacts max.: 4 NO contacts Width: 22,5mm Cross fault detection: Yes SIL CL acc. to IEC/EN 62061: 3 Approvals: UL Nominal voltage: AC, AC/DC Thermal current Ith max.: 8A Type: LG 5925 Manufacturer: E. Dold & Söhne GmbH & Co. KG Type: LG5925.48/61 AC/DC24V Art. No.: 0061919