Output module with output contacts BG 5912 Realization of fail-safe control circuits for protection of people and machinery. Features . According to - Performance Level (PL) e and category 4 to EN ISO 13849-1: 2008 - SIL Claimed Level (SIL CL) 3 to IEC/EN 62061 - Safety Integrity Level (SIL 3) to IEC/EN 61508 . Safety outputs can be assigned to one or several function modules (control unit or input modules). . Outputs: - 4 NO contacts - 3 NO contacts, 1 NC contact - 3 NO contacts 0-3 s delay-release time-delay relay - 2 NO contacts, 1 NC contact 0-3 s delay-release time-delay relay . Permanently monitored feedback loop for external contact reinforcement . LEDs for status indication . Width 22.5 mm Technical specifications Cat. / PL acc. to EN ISO 13849-1: 4/e Width: 22,5mm SIL CL acc. to IEC/EN 62061: 3 Safe output contacts, redundant NO contacts: 3, 4 Safe output contacts, time delay: 3, 2 Type: BG 5912 Manufacturer: E. Dold & Söhne GmbH & Co. KG Type: BG5912.04/00000 DC24V Art. No.: 0056402