Delay module, release delayed LG 7928 The LG 7928 can be used for delayed stopp with status request of the safety relays (Stop category 1 acc. to DIN EN 60 204-1) or controlled stopping of plant components. Advantages . Easy to realise safe timing circuits . 4 forcibly guided output contacts at only 22.5 mm width Features . According to - Performance Level (PL) d and category 3 to EN ISO 13849-1 - SIL Claimed Level (SIL CL) 2 to IEC/EN 62061 - Safety Integrity Level (SIL) 2 to IEC/EN 61508 and IEC/EN 61511 when connected to a suitable safety module . Adjustable time delay . As option fixed time delay . High long life stability due to digital time base . Adjustable with or without cross fault detection . Output: 3 NO contacts + 1 NC contact + 1 forcibly guided feedback contact or 4 NO contacts + 1 forcibly guided feedback contact . LED indicator for channel 1, 2 and operation voltage . Wire connection: also 2 x 1.5 mm2 stranded ferruled, or 2 x 2.5 mm2 solid DIN 46228-1/-2/-3/-4 . As option with pluggable terminal blocks for easy exchange of devices - with screw terminals - or with cage clamp terminals . Width 22.5 mm Technical specifications Cat. / PL acc. to EN ISO 13849-1: 3/d 1- / 2-channel: 1 Connection: Screw terminals, Pluggable screw terminals, Pluggable cage clamp terminals Output contacts max.: 1 NC contact, 4 NO contacts Width: 22,5mm SIL CL acc. to IEC/EN 62061: 2 Approvals: UL Time delay max.: 600s Nominal voltage: AC/DC Thermal current Ith max.: 5A Type: LG 7928 Manufacturer: E. Dold & Söhne GmbH & Co. KG Type: LG7928.97/61 AC/DC24V 1-10S Art. No.: 0062796