Over- and Undercurrent Relay SP 9277CT . Over- and undercurrent detection in single phase or 3-phase voltage systems . For industrial and railway applications Features . According to IEC/EN 60 255-1 . IP 9277, SP 9277, SP 9277CT: 3-phase IL 9277, SL 9277, SL 9277CT: singele phase . Detects over- and undercurrent . Measuring ranges from 0.1 ... 15 A . With built in current transformer for 0.5 ... 100 A . IL 9277, SL 9277 with 4 programmable ranges . Settable 0.1 ... 1 IN . Separate setting for over- and undercurrent . Fixed hysteresis approx. 4 % . Settable time delay . IP 9277, SP 9277 with separate settable time delay for over- and undercurrent . De-energized on trip . LED indicators for over-, under- and normal current . Auxiliary supply and measuring input galvanic separated . IL 9277, SL 9277 with one output relay for over- and undercurrent . IP 9277, SP 9277 with separate output relays for over- and undercurrent . Optionally energized on trip . Devices available in 2 enclosure versions: - I-model, e.g. IL _ _ _ _, depth 61 mm with terminals at the bottom for installations systems and industrial distribution systems according to DIN 43 880 - S-model, e.g. SL _ _ _ _, depth 100 mm with terminals at the top for cabinets with mounting plate and cable duct . DIN rail or screw mounting . Width IL 9277, SL 9277, SL 9277CT: 35 mm IP 9277, SP 9277, SP 9277CT: 70 mm Technical specifications Width: 70mm Operate delay: Yes Enclosure design: Switch cabinet 1- / 3-phase: 3 Output contacts: 2 x 2 C/O contacts Auxiliary voltage: AC, AC/DC Type: SP 9277CT Measuring range: AC 0,5 - 100A Manufacturer: E. Dold & Söhne GmbH & Co. KG Type: SP9277.39CT AC220-240V 10-100A Art. No.: 0059427