Neutral Monitor SL 9069 The IL/SL9069 neutral monitors in the VARIMETER series monitor the neutral conductor in electrical systems and three-phase networks. Monitoring is simple and does not require a great deal of wiring, as no auxiliary voltage is required. The detection of a missing neutral conductor, a phase or a reversal of the neutral conductor with a phase prevents costly damage and as a user you benefit from the operational safety and high availability of your system. Advantages . Protects systems from damage caused by excessively high or low voltages with unbalanced loads . Preventive maintenance . For better productivity Features . According to IEC/EN 60255-1 . Detection of - Missing neutral in the system - Broken neutral on IL/SL 9069 - Neutral exchanged against phase . Detection of phase failure also with disconnected load . For 3-phase systems . De-energized on trip . LED indicator for operation/state of output contacts . Single phase connection possible . Without auxiliary voltage . 2 cangeover contacts . Optionally with adjustable asymmetry detection and on delay . Devices available in 2 enclosure version: IL 9069: Depth 59 mm with terminals at the bottom for installations systems and industrial distribution systems according to DIN 43880 SL 9069: Depth 98 mm with terminals at the top for cabinets with mounting plate and cable duct . Width 35 mm Technical specifications Width: 35mm Operate delay: Yes Enclosure design: Switch cabinet 1- / 3-phase: 3 Standard measuring range: 3/N AC 400/230 V Measuring range max.: 415 V Output contacts: 2 C/O contacts Type: SL 9069 Manufacturer: E. Dold & Söhne GmbH & Co. KG Type: SL9069.12 3/N AC220/127V Art. No.: 0050635