Extension module LG 5929 If more safety cicuits have to be switched, than a safety module provides, the extension module LG 5929 is used. It offers safe and reliable contact multiplication and re-enforcment for safety modules with monitoring of the feedback circuit. Safe semiconductor outputs can be extended by relay output contacts. The extension module has forcibly guided contacts and can be delivered with different contact arrangements. Advantages . Safety contact multiplication Features . According to - Performance Level (PL) e and category 4 to EN ISO 13849-1 - SIL Claimed Level (SIL CL) 3 to IEC/EN 62061 - Safety Integrity Level (SIL) 3 to IEC/EN 61508 when connected to a suitable safety module . According to EN 50156-1 for furnaces . Control from semiconductor safety outputs (light curtains, e-stop, etc.) is also possible . Redundant and forcibly guided contacts . Output: max. 5 NO contacts or 4 NO contacts / 1 NC contact . 1-channel or 2-channel connection . LED indication for operation . Removeable terminal strips . Wire connection: also 2 x 1.5 mm2 stranded ferruled, or 2 x 2.5 mm2 solid DIN 46 228-1/-2/-3/-4 . As option with pluggable terminal blocks for easy exchange of devices - with screw terminals - or with cage clamp terminals . Width 22.5 mm Technical specifications Cat. / PL acc. to EN ISO 13849-1: 4/e 1- / 2-channel: 1, 2 Connection: Screw terminals, Pluggable screw terminals, Pluggable cage clamp terminals Output contacts max.: 1 NC contact, 5 NO contacts Width: 22,5mm SIL CL acc. to IEC/EN 62061: 3 Approvals: UL Nominal voltage: AC, AC/DC Thermal current Ith max.: 5A Type: LG 5929 Manufacturer: E. Dold & Söhne GmbH & Co. KG Type: LG5929.60/100/61 AC/DC24V Art. No.: 0061923