IP 9110/107

Undervoltage relay

IP 9110/107

Contacts

Nominal voltage

Time delay

Response value

Variant

  • 0048884
  • IP9110.11/117 3/N AC400/230V 0,9UN
Undervoltage relay, for medical rooms. more

Product description

Undervoltage relay, for medical rooms.

Technical specifications

Width: 70 mm
1- / 3-phase: 1, 3
Nominal voltage max.: 3/N AC 400 / 230 V
Auxiliary voltage: Without
Output contacts: 1 C/O contact, 1 NO contact, 1 NC contact
Enclosure design: Distribution board
Type: IP 9110/107

Features

  • nach IEC/EN 60 255-1
  • nach DIN VDE 0100-710, für medizinisch genutzte Räume
  • Im Drehstromnetz werden erkannt:
    - Unterspannung
    - Phasenausfall
    - Neutralleiterbruch
    - Spannungsasymmetrie und Rückspeisung
  • 3 Prüftasten zur Simulation der Unterspannung
  • hohe Überlastbarkeit
  • auch einphasig anschließbar
  • Ruhestromprinzip (Ausgangsrelais im Fehlerfall nicht aktiviert)
  • LED-Anzeige
  • Phasenfolge beliebig
  • wahlweise mit Zeitverzögerung tv
  • wahlweise
    - 1 Wechsler, 1 Schließer, 1 Öffner oder
    - 1 Wechsler verzögert
  • 70 mm Baubreite