Cookie preferences
This website uses cookies, which are necessary for the technical operation of the website and are always set. Other cookies, which increase the comfort when using this website, are used for direct advertising or to facilitate interaction with other websites and social networks, are only set with your consent.
Configuration
Technically required
These cookies are necessary for the basic functions of the shop.
"Allow all cookies" cookie
"Decline all cookies" cookie
CSRF token
Cookie preferences
Currency change
Customer recognition
Customer-specific caching
Individual prices
Selected shop
Session
Comfort functions
These cookies are used to make the shopping experience even more appealing, for example for the recognition of the visitor.
Note
Show the facebook fanpage in the right blod sidebar
Statistics & Tracking
Affiliate program
Google Tag Manager
Track device being used
Short-time Voltage Drop Relay
SL 9079
- Article number: 0054172
- Type: SL9079.12/103 3AC400V 0,8-1,05UN
Monitoring of voltage systems to detect auto reclosing as e.g. generated by the energy supplier... more
Product description
Monitoring of voltage systems to detect auto reclosing as e.g. generated by the energy supplier in the case of flash-overs or switching procedures. It is possible that in control circuits some of the devices are resetted during auto reclosing and some not. Because of this uncontrollable situations may occur. By detecting these fast auto reclosings and addition of a certain time delay at reclosing the OFF-time is lengthened and every device has the time to reset. The circuit goes into a defined OFF state and is automatically resetted after the adjusted time delay or by manual reset if the automatic reset is disabled by an external circuit.
Technical specifications
Width: | 35 mm |
Operate delay: | Yes |
1- / 3-phase: | 1, 3 |
Nominal voltage max.: | 3 AC 500 V |
Auxiliary voltage: | Without |
Output contacts: | 2 C/O contacts |
Enclosure design: | Switch cabinet |
Type: | SL 9079 |
Features
- According to IEC/EN 60255-1
- Fast detection of undervoltage or phase failure in three-phase voltage systems
- Detects auto reclosing of 20 ms
- Adjustable response value 0.55 ... 1.05 UN
- Operate delay to generate a defined reset signal
- Manual reset possible with external circuit
- Single-phase connection possible
- Optionally fixed response value 0.8 UN
- De-energized on trip
- Green LED indicate for closed contact
- Independant of phase sequence
- 3p4w connection
- Optionally for 3p3w systems
- 2 changeover contacts
- Devices available in 2 enclosure versions:
IL 9079: Depth 59 mm, with terminals at the bottom for installation systems and industrial distribution systems according to DIN 43880
SL 9079: Depth 98 mm, with terminals at the top for cabinets for mounting plate and cable duct - Width 35 mm