Cookie preferences
This website uses cookies, which are necessary for the technical operation of the website and are always set. Other cookies, which increase the comfort when using this website, are used for direct advertising or to facilitate interaction with other websites and social networks, are only set with your consent.
Configuration
Technically required
These cookies are necessary for the basic functions of the shop.
"Allow all cookies" cookie
"Decline all cookies" cookie
CSRF token
Cookie preferences
Currency change
Customer recognition
Customer-specific caching
Individual prices
Selected shop
Session
Comfort functions
These cookies are used to make the shopping experience even more appealing, for example for the recognition of the visitor.
Note
Show the facebook fanpage in the right blod sidebar
Statistics & Tracking
Affiliate program
Google Tag Manager
Track device being used
Emergency stop module with time delay
LG 5928
- Article number: 0061683
- Type: LG5928.41/61 DC24V 1-10S
Protection of people and machines Emergency stop circuits on machines, Stop category 1 can... more
Product description
- Protection of people and machines
- Emergency stop circuits on machines, Stop category 1 can be realised
- Monitoring of safety gates
Technical specifications
Width: | 22,5 mm |
Cat. / PL acc. to EN ISO 13849-1: | 4/e |
SIL CL acc. to IEC/EN 62061: | 3 |
Nominal voltage: | DC |
Suited as safety gate monitor: | Yes |
Thermal current Ith max.: | 8 A |
1- / 2-channel: | 1, 2 |
Cross fault detection: | Yes |
Connection: | Screw terminals, Pluggable screw terminals, Pluggable cage clamp terminals |
Output contacts max.: | 2 NO contacts, 1 NO contact delayed |
Approvals: | UL |
Type: | LG 5928 |
Downloads
Advantages
- Compact, flexible and safe
- Short response time
- Ideal for designs according to the new safety standards
Features
- According to
- Performance Level (PL) e and category 4 to EN ISO 13849-1
- SIL Claimed Level (SIL CL) 3 to IEC/EN 62061
- Safety Integrity Level (SIL) 3 to IEC/EN 61508 and IEC/EN 61511 - Output: 2 NO instantaneous contacts and 1 release delay contact
- 1- or 2-channel connection
- Line fault detection at the ON pushbuttons at connection on terminals S33-S34
- Manual restart with button on S33-S34 or automatic restart with bridge between S13-S34
- With or without cross fault monitoring in the E-stop loop
- Indication for released time circuit
- LED indication for supply, channel 1/2 and release delayed contacts
- Wire connection: also 2 x 1.5 mm2 stranded ferruled (isolated), DIN 46228-1/-2/-3/-4 or 2 x 2.5 mm2 stranded ferruled DIN 46228-1/-2/-3
- As option with pluggable terminal blocks for easy exchange of devices
- with screw terminals
- or with cage clamp terminals - Width 22.5 mm